Front Panel,Process Value,parameter type,SetPoint YOKOGAWA YOKOGAWA. indicator PV SetPoint no SetPoint,indication PV,SP Auto Man SP2 3 4. indication,SP2 3 4 MAN,Alarm LED s SP Auto Man,indication. LED s UT320 Auto Man key AL1 2 3 4 MAN,A M Set Enter A M. Set keys Set keys,UT320 UT350,Key Function, Set Enter Used to select a parameter or set a parameter Hold down for.
3 seconds to enter the configuration mode, Used to select automatic or manual mode The setting toggles. A M between auto and manual with each keystroke, Used to change values Pressing and holding causes the. speed of charging to increase,Configuration, It is important that the controller be set up in the following manner Failure to do so could result. in incorrect operation as changing some parameters will change other related functions. 1 Apply power See Wiring Diagram pg 16,2 Set I O parameters. 3 Set functional parameters,4 Set operation parameters.
5 Operate process,6 Set a reasonable medium setpoint. 7 Turn AUTOTUNE parameter AT on,Parameter Flow Charts. The UT320 UT350 have a number of software parameters which may or may not be required depending. on your particular application,Operating Display,Press the SET ENT for 3 seconds. OP PA STUP These are the,input output,Press the key. parameters,set them first,LL Press the SET ENT key for less than.
3 seconds to move between any of the,parameters,1 P 2 P 3 P 4 P SPH IN. SC 1 l 2 l 3 l 4 l UNIT,SP NO 1 D 2 D 3 D 4 D RH,1 MR 2 MR 3 MR 4 MR AL2 RL. 1 Pc 2 Pc 3 Pc 4 Pc AL3 SDP,1 lc 2 lc 3 lc 4 lc HY1 SH. 1 Dc 2 Dc 3 Dc 4 Dc HY2 SL,1 DB 2 DB 3 DB 4 DB HY3 RJC. 1 RP 2 RP RDV DY1 BSL,BS DY3 RET,UPR CT RTH,These are the.
DNR functional CTc RTL,parameters,OL second POc C S1. H C MD C S2,DR ZON C S3,These are the,HB1 operating AR C S4. parameters They,HB2 may be set after TMU LOCK,HC1 I O and functional P SL PWD. parameters,INPUT OUTPUT I O MENU,Default CS,Symbol Description Range Explanation. Input type Select from table 1 1 Sets the type of input such as 1201. IN type K T C PT100 RTD 1, Input unit selection F C C Select from F or C look up 1202.
UNIT tables for T C or RTD Not,Used for linear inputs. Range high See table 1 Max of input range Max Min of selected range 1204. RH selected in table 1 May be,set to any number in that. Range low See table 1 Min of input range See explanation above 1205. Scale decimal point Only available for 1 Selects the number of digits 1206. SDP selection DC voltage inputs 0 displayed to the right of the. to 3 decimal Limits 0 1999,to 9999 1 199 9 to 999 9. 3 19 99 to 99 99, Scale high only for DC voltage 1999 to 100 0 when DC Allows setting of properly 1207. SH voltage inputs 9999 voltage is selected scaled units for flow level. pH etc If 1 to 5VDC,represents 0 to 250 then set,SH to 250 and SL to 0.
Scale low only for DC voltage 1999 to 0 0 when DC See explanation above 1208. SL voltage inputs 9999 voltage is selected, Reference junction OFF ON ON RJC must be on for TC 1210. RJC compensation inputs to read properly It is,not used for RTD or DCV. Burnout selection 0 OFF 1 upscale 1 Determines which way the 1209. BSL 2 downscale PV will drive when the input,circuit is opened 1 will. cause the PV to drive to max,and display burnout 2 will. cause the PV to drive to min,and display burnout When.
the input is in B OUT the,controller goes to a preset. output PO POc, Output type 0 Relay 0 Sets the control output type 1238. OT 1 Voltage pulse as determined table 2 For,2 Current UT320 350 0X only types. 0 3 are available For,3 ON OFF control,UT320 350 2X units all of. 4 to 12 Heating the output types are,Cooling control available.
Retransmission type 1 PV 2 SP 3 OUT 1 Selects what is retransmitted 1013. RET 4 LPS power to a recorder or other analog,supply for sensor device Also selects. whether loop power supply,INPUT OUTPUT I O MENU Cont. Symbol Description Range Explanation CS, Retransmission high EU 0 0 to 100 RH value Max value for the 1014. RTH RTL RTH retransmitted output, Retransmission low EU 0 0 to 100 RL value Min value for the 1015. RTL RTL RTH retransmitted output, Digital input selection 0 Disables the 1 All UT320 350 controllers 932.
DIS contact inputs have 2 digital inputs They,1 DI1 2 SP on can be used to perform the. 1 SP off DI2 described functions,AUTO on MAN,2 DI1 Hides on. shows off LOCK,3 See note 1,4 DI1 2 SP on,1 SP off DI2. STOP on RUN off, Custom SELECT Custom SELECT OFF Up to 4 parameters may N A. C S1 display 1 selection display definition be set for operator access. Allows access to any They may then be viewed,selected parameter by pressing the SET ENT.
key during normal,operations,Custom SELECT See above OFF See above N A. C S2 display 1 selection,Custom SELECT See above OFF See above N A. C S3 display 1 selection,Custom SELECT See above OFF See above N A. C S4 display 1 selection, Key lock OFF 1 All parameter OFF Restricts access to various 1036. LOCK changes prohibited 2 functions by locking out. Changes to operating certain keys,parameters prohibited.
3 A M key disabled,Password 0 OFF 0 Password prohibits access N A. PWD 1 9999 to setup menus FUNC and,I O for those that don t. know the password,Note 1 SP selection when DIS 3 set. 1 SP OFF OFF,2 SP ON OFF,3 SP OFF ON,4 SP ON ON 5,FUNCTION Func MENU. Symbol Description Range Explanation CS, Target setpoint limiter 0 0 to 100 0 of 100 of PV input Places a limit on how high 933.
SPH upper limit PV input range range the setpoint can be set. where SPL SPH, Target setpoint limiter 0 0 to 100 0 of 0 of PV input Places a limit on how low 934. SPL lower limit PV input range range the setpoint can be set. where SPL SPH, Alarm 1 type OFF 1 to 25 28 1 Sets the type of alarm 915. AL1 to 31 action as described in table,See Table 3 3. Alarm 2 type See above 2 See above 916,Alarm 3 type see Note 1 See above 1 See above 917. Alarm 1 hysteresis EUS 0 0 to EUS 0 5 Sets the dead band of the 919. HY1 100 0 alarm to avoid relay,chattering or frequent.
ON OFF activation Set in,engineering units, Alarm 1 hysteresis See above See above See above 920. Alarm 1 hysteresis see See above See above See above 921. HY3 Note 1, Alarm 1 delay timer 0 00 to 99 59 0 00 An alarm is output when 935. DY1 min sec the delay timer expires,enabled when after the alarm setpoint is. AL1 is 1 to 20 or reached,Alarm 2 delay timer See above 0 00 See above 936. Alarm 3 delay timer See above 0 00 See above 937, Control output cycle time 1 to 1000 seconds 30 seconds For time proportional 1240.
CT see Note 1 outputs only Selects the,total on and off time. Control output cycle time 1 to 1000 seconds 30 seconds For time proportional 1241. CTc for cooling side see note outputs only Selects the. 2 total on and off time, Note 1 When control output setup parameter OT is set from 4 to 6 for heating cooling type the functions for. alarm 3 will be invalid ALM3 is used for cooling, Note 2 These parameters will be displayed when heating cooling control is selected. FUNCTION Func MENU Cont,Description Range Default,Symbol Explanation CS. Preset output 5 0 to 105 0 0 0 to 0 0 The output used when the 924. PO 105 0 in input sensor is in a burn,heating cooling out condition open.
control sensor,Preset output for 0 0 to 105 0 0 0 See above 925. POc cooling side see Note, PID control mode 0 Batch 0 Selects between derivative 927. C MD 1 Fixed value of deviation 0 or PV,derivative 1 PID which. reduces the disturbances,caused by setpoint changes. If setpoint changes are,made during operation set,to 1 otherwise set to 0.
Zone PID selection OFF SP number OFF Selects between SP or zone 929. ZON selection selected PID For SP PID,ON Zone PID SP1 uses PID1 SP2 uses. PID2 etc For Zone PID,PID is selected,automatically depending. on the PV and reference,points in each PID set, Anti reset wind up AUTO AUTO Eliminates the I term effect 928. AR 50 0 to 200 0 from leaving controller,operating while system is. turned off In most cases,Auto is the correct choice.
Time unit for ramp 0 Hour 0 Sets the time units used by 904. TMU 1 Minute the UPR and DNR prompts,in the operating parameter. Protocol selection 0 PC link 0 0 Connection to PC basic 1247. P SL see Note 2 1 PC link check sum module or touch screen. 2 Ladder comm 1 Same as 0 but adds,3 Master unit check sum capability. 4 Slave unit 2 Direct connection to,devices supporting BCD. 7 Modbus ASCII,3 4 SP from master unit,8 Modbus RTU is sent to slave units. Note 1 These parameters will be displayed when heating cooling control is selected. Note 2 These parameters will be displayed on models with the optional RS485 interface UT3 0 1. See additional information in the appendix,FUNCTION Func MENU Cont.
Symbol Description Default,Range Explanation CS, Communication speed 0 600 1 1200 2 4 In most cases these comm 1248. BPS see Note 1 2400 3 4800 4 Parameters do not need to. 9600 be adjusted other than the,address Check the driver. or the software package for,exact requirements,Parity see Note 1 0 None 1 Even 1 See above 1249. Stop bit see Note 1 1 2 1 See above 1250,Data length see Note 1 7 or 8 8 See above 1251. Address see Note 1 1 to 99 limited to 1 See above 1252. ADR a max of 31 units,Min response time 0 to 10 x 10ms 0 See above 1253.
RP T see Note 1, Note 1 These parameters will be displayed on models with the optional RS485 interface UT3 0 1. Operating Parameters,Default Explanation CS,Symbol Description Range. LL communication OFF 0 RS485 OFF 0 Used to choose comm N A. LL interface selection terminals method for using LL100. ON 1 Light loader configuration software, Setpoint value for Process variable and Process This is the setpoint for the 231. A1 alarm 1 setpoint value EU variable and alarms and is set in. 100 0 to 100 0 setpoint value engineering units used. Deviation EUS EU 100 like F,100 0 to 100 0 Other PV and. Output value 5 0 setpoint values,to 105 0 EU 0,Deviation 0.
Setpoint value for See above See above See above 232. A2 alarm 2, Setpoint value for See above See above See above 233. A3 alarm 3,see Note 1, Auto tuning OFF 1 to 4 by group OFF Auto tuning will disturb 241. AT for PID 1 to 4 your process 3 times to,AUTO only for zone learn it s performance. PID characteristics and then set,the optimal PID values for. control 1 sets PID1 2 sets,PID2 ETC AUTO sets,all 4 PID sets.
Super control OFF ON OFF Uses fuzzy logic to 242,SC eliminate overshoot and. improve control,performance It should be,ON in most cases. Selection of setpoint 1 to 4 1 Up to 4 preset setpoints 207. SP NO number that can be switched by,external DI RS485 or. front face, PID parameter number 0 Transition to 0 Provides access to the 4 N A. PID parameter screen 1 to PID sets in each controller. 4 All PID sets are 1 PID set 1 2 PID set 2,displayed etc.
PV input filter OFF 1 to 120 sec OFF Helps settle down an 244. FL erratic PV display input,Use the smallest filter to. get a smooth result,Excessive filter can be, PV input bias EUS 100 0 to EUS 0 0 Corrects the PV reading 243. BS 100 0 for poor sensor placement,or sensor errors. Note 1 When control output setup parameter OT is set from 4 to 6 for heating cooling type the. functions for alarm 3 will be invalid ALM3 is used for cooling. See additional information in appendix 9,Operating Parameters cont. Symbol Description Range Explanation CS, Setpoint value OFF EUS 0 to OFF In effect any time the 245.
UPR increasing ramp rate 100 Hours or setpoint is changed or after. minutes a power failure When the,power comes on the SP. will be the same as the PV,It will then ramp to the. correct SP based on these,Setpoint value See above OFF See above 246. DNR decreasing ramp rate, Output high limit OL 1 digit to 100 0 Limits the output when the 254. OH 105 0 0 0 to process system cannot,105 During tolerate max or min ouput.
heating cooling levels, Output low limit 5 0 to OH 1 0 0 100 0 See above 255. OL digit 0 0 to 105 during heating,During heating cooling control. cooling control, Hysteresis of ON OFF EUS 0 0 to 100 0 EUS 0 5 0 1 Dead band of the control 256. H control 0 1 to 0 5 during heating output Only in effect. During heating cooling control when on off control. cooling control OT 3 is selected, Direct reverse action 0 Reverse 0 Sets the control response 257. DR selection see Note 1 1 Direct Reverse as PV exceeds. SP output decreases,Direct as PV exceeds SP,output increases.
Heater break alarm 1 OFF 1 to 50A OFF Setpoint at which the HB 258. HB1 current setpoint alarm is a activated Set,see note 2 this value in amps. Heater break alarm 2 OFF 1 to 50A OFF See above 259. HB2 current setpoint,see note 2, Heater disconnection Read only Allows reading the current. HC1 alarm 1 measured 1 to 50 mA flowing through a CT. current see Note 2,Heater disconnection Read only,HC2 alarm 2 measured 1 to 50 mA. current see Note 2, Note 1 During heating cooling control the heating output is fixed as reverse action and the cooling output is. UT320E UT350E SHORT FORM INSTRUCTION MANUAL ENHANCED Congratulations on your purchase of the finest program controller available This short form guide is designed to speed up your configuration and operation For additional information please refer to the Instruction Manual on CD ROM provided with the controller