4100ES Addressable Fire Detection and Control Basic Panel Modules and Accessories. phased expansion with future equipment and devices grouped into. a single trouble operators can more clearly identify events from the. commissioned and occupied areas, Module level ground fault searching assists installation and service by. locating and isolating modules with grounded wiring. Recurring Trouble Filtering allows the panel to recognize process. and log recurring intermittent troubles such as external wiring ground. faults but only sends a single outbound system trouble to avoid. nuisance communications, WALKTEST silent or audible system test performs an automatic self. resetting test cycle,Introduction, 4100ES Series Fire Detection and Control Panels provide extensive. installation operator and service features with point and module. capacities suitable for a wide range of system applications An on. board Ethernet port provides fast external system communications. to expedite installation and service activity Dedicated compact flash. memory archiving provides secure on site system information storage of. electronic job configuration files,Modular design, A wide variety of functional modules are available to meet specific. system requirements Selections allow panels to be configured for either. Stand Alone or Networked fire control operation InfoAlarm Command. Center options provide convenient expanded display content detailed. on data sheet S4100 0045,Module Bay Description, The Master Controller Bay top includes a standard multi featured.
system power supply the master controller board and operator. interface equipment, The Expansion Bays include a Power Distribution Interface PDI for. new 4 in x 5 in flat design option modules and also accommodate. 4100 style modules, The Battery Compartment bottom accepts two batteries up to 50. Ah to be mounted within the cabinet without interfering with module. The following illustration identifies bay locations using a three bay. cabinet for reference Figure 2 4100ES Module Bay Reference. Page 2 S4100 0031 Rev 42 11 2019, 4100ES Addressable Fire Detection and Control Basic Panel Modules and Accessories. Mechanical Description waterflow switches can be interfaced to the addressable controller to. Boxes can be close nippled each box provides convenient stud communicate their identity and status. markers for drywall thickness and nail hole knockouts for quicker Addressability allows the location and condition of the connected device. mounting to be displayed on the operator interface LCD and on remote system. Smooth box surfaces are provided for locally cutting conduit entrance annunciators Additionally control circuits fans dampers etc may be. holes exactly where required individually controlled and monitored with addressable devices. Cabinet assembly design has been seismic tested and is certified to Addressable Operation. IBC and CBC standards as well as to ASCE 7 categories A through F Each addressable device on the communication channel is continuously. requires 4100 7912 option for additional legacy card stabilizer brackets interrogated for status condition such as normal off normal alarm. and battery brackets as detailed on data sheet S2081 0019 supervisory or trouble Both Class B and Class A operation are available. The latching dress panel retainer assembly easily lifts off for internal Sophisticated poll and response communication techniques ensure. access supervision integrity and allow for T tapping of the circuit for Class. NACs are mounted directly on power supply assemblies providing B operation Devices with LEDs pulse the LED to indicate receipt of a. minimized wiring loss compact size and readily accessible communications poll and can be turned on steady from the panel. terminations,IDNet Channel Capacity, Packaging supports traditional 4100 style motherboard with daughter. The CPU bay system power supply SPS provides an IDNet signaling line. circuit SLC that supports up to 250 addressable monitor and control. Modules are power limited except as noted such as relay modules points intermixed on the same pair of wires Additional 250 point IDNet. The NEMA 1 IP30 box is ordered separately and available for early circuit modules are available see Table 16. installation,Table 1 IDNet MAPNET II IDNet 2 and, Doors are available with tempered glass inserts or solid boxes and IDNet 2 2 SLC Wiring Common Specifications.
doors are available in platinum or red,Specification Description. Boxes and door retainer assemblies are ordered separately per system. Maximum Distance 1 to 125 4000 ft 1219 m 50 ohms, requirements refer to data sheet S4100 0037 for details. from Control Panel per 126 to,2500 ft 762 m 35 ohms. Device Load 250, Operator Interface Detail Reference Terminals for 18 to 12 AWG 0 82. The following illustration identifies the primary functions of the operator Connections 2 2. mm to 3 31 mm,Table 2 IDNet and MAPNET II Specifications.
Specification Description,Preferred Shielded twisted pair STP. Acceptable Unshielded twisted pair UTP,IDNet and MAPNET II Wiring Total. Wire Length Allowed With T Taps Up to 10 000 ft 3 km 0 58 F. for Class B Wiring, Table 3 IDNet 2 and IDNet 2 2 Wiring Specifications. Specification Description,Shielded or unshielded twisted or. untwisted wire,Total Wire Length Allowed With T,Up to 12 500 ft 3 8 km 0 60 F.
Taps for Class B Wiring,Maximum Capacitance Between. IDNet 2 Channels, IDNet 2 and IDNet 2 2 Module Compatibility IDNet communicating. devices and TrueAlarm sensors including QuickConnect and. QuickConnect2 sensors,Figure 3 Operator Interface Detail Reference. Note Some applications may require shielded wiring Review your sys. tem with your local Simplex product supplier,Compatible Peripheral Devices. The 4100ES is compatible with an extensive list of remote peripheral. devices including printers CRT keyboards up to five total and both TrueAlarm System Operation. conventional and addressable devices including TrueAlarm analog Addressable device communications include operation of TrueAlarm. sensors smoke and temperature sensors Smoke sensors transmit an output. value based on their smoke chamber condition and the CPU maintains a. current value peak value and an average value for each sensor Status. Addressable Device Control, is determined by comparing the current sensor value to its average.
Overview value Tracking this average value as a continuously shifting reference. The 4100ES provides standard addressable device communications point filters out environmental factors that cause shifts in sensitivity. for IDNet compatible devices and accepts optional modules for Programmable sensitivity of each sensor can be selected at the. communications with MAPNET II compatible devices Using a two wire control panel for different levels of smoke obscuration shown directly. communications circuit individual devices such as manual fire alarm in percent or for specific heat detection levels To evaluate whether the. stations TrueAlarm sensors conventional IDC zones and sprinkler sensitivity should be revised the peak value is stored in memory and can. be easily read and compared to the alarm threshold directly in percent. Page 3 S4100 0031 Rev 42 11 2019, 4100ES Addressable Fire Detection and Control Basic Panel Modules and Accessories. CO sensor bases combine an electrolytic CO sensing module with a Provides system power battery charging auxiliary power auxiliary. TrueAlarm analog sensor to provide a single multiple sensing assembly relay earth detection on board IDNet communications channel for. using one system address The CO sensor can be enabled disabled 250 points three on board NACs and provisions for either an optional. used in LED Switch modes and custom control and can be made public City Connect Module or an optional Alarm Relay Module. for communication across a fire alarm Network For more details refer IDNet SLC Output provides Class B or Class A communications for. to data sheet S4098 0052 up to 250 addressable devices as described in Addressable Device. TrueAlarm heat sensors can be selected for fixed temperature Control. detection with or without rate of rise detection Utility temperature Three 3 A On Board NACs conventional reverse polarity operation. sensing is also available typically to provide freeze warnings or alert to rated 3 A for Special Application appliances and 2 A for Regulated. HVAC system problems Readings can selected as either Fahrenheit or 24 DC power with electronic control and overcurrent protection. Celsius selectable as Class B or Class A and for synchronized strobe or. SmartSync horn strobe operation over two wires,TrueSense Early Fire Detection. NACs are selectable as auxiliary power outputs derated to 2 A for. Multi sensor 4098 9754 provides photoelectric and heat sensor data. continuous duty total auxiliary power output per SPS is limited to 5 A. using a single 4100ES IDNet address The panel evaluates smoke. activity heat activity and their combination to provide TrueSense Battery Charger is dual rate temperature compensated and. early detection For more details on this operation refer to data sheet charges up to 50 Ah sealed lead acid batteries mounted in the battery. S4098 0024 compartment 33 Ah for single bay cabinets also is UL listed for. charging up to 110 Ah batteries mounted in an external cabinet refer. to data sheet S2081 0012 for details,Diagnostics and Default Device Type. Battery and Charger Monitoring includes battery charger status. Sensor Status and low or depleted battery conditions status information provided. TrueAlarm operation allows the control panel to automatically indicate to the master controller includes analog values for battery voltage. when a sensor is almost dirty dirty and excessively dirty The NFPA 72 charger voltage and current actual system voltage and current and. requirement for a test of the sensitivity range of the sensors is fulfilled individual NAC currents. by the ability of TrueAlarm operation to maintain the sensitivity level of 2 A Auxiliary Power Output is selectable for detector reset door. each sensor CO Sensors track their 10 year active life status providing holder or coded output operation. indicators to assist with service planning Indicators occur at 1 year 6 Auxiliary Relay is selectable as N O or N C rated 2 A 32 VDC. months and when end of life is reached and is programmable as a trouble relay either normally energized or. Modular TrueAlarm sensors normally de energized or as an auxiliary control. TrueAlarm sensors use the same base and different sensor types smoke Optional City Connect Module 4100 6031 with disconnect. or heat sensor and can be easily interchanged to meet specific location switches or 4100 6032 without disconnect switches can be selected. requirements This allows intentional sensor substitution during building for conventional dual circuit city connections. construction when conditions are temporarily dusty Instead of covering Optional Alarm Relay Module 4100 6033 provides three Form. smoke sensors causing them to be disabled heat sensors may be C relays that are used for Alarm Trouble and Supervisory rated 2 A. installed without reprogramming the control panel The control panel resistive 32 VDC. will indicate an incorrect sensor type but the heat sensor will operate at. 8 Point Zone Relay Module Details, a default sensitivity to provide heat detection for building protection at. that location Select as IDC or Relay configure up to eight Class B IDCs or up to. four Class A IDCs or up to eight Relay outputs rated 2 A resistive 30. VDC N O or N C or combinations of IDCs and Relays each zone is. CPU Bay Module Details separately configurable as an IDC or Relay output. Master Controller and Motherboard IDC Support each IDC supports up to 30 two wire devices Zone relay. Mounts in Slot 4 of a two slot motherboard Slots 3 and 4 of the modules may be powered directly from the control unit power supply. Master Controller Bay and provides one Class B or Class A RUI or through the optional 25 VDC regulator module where required for. communications channel configurable for isolated or un isolated two wire detector compatibility Refer to 2 Wire Detector Compatibility. operation document 579 832 for additional details, Slot 3 of the motherboard is primarily for a modular network interface IDC EOL resistor values are selectable as 3 3 k 2 k 2 2 k 3 4 k.
card or secondarily for the 4100 6038 dual RS 232 board 3 9 k 4 7 k 5 1 k 5 6 k 6 34 6 8 k and 3 6 k 1 1 k see. instructions for more details, RUI communications controls up to 31 devices per master controller. on one or multiple RUI and RUI channels devices include MINIPLEX. transponders 4603 9101 LCD Annunciators 4602 9101 Status. Command Units SCU 4602 9102 Remote Command Units RCU. 4602 Series LED Annunciator Panels and 4100 Series 24 I O and LED. Switch modules, Note 4602 series annunciators require un isolated communications. Up to four RUI channels combination of built in RUI and optional RUI. modules are supported per master controller, Optional Service Modem 4100 6030 mounts onto the master. controller board with its own on board connections. System Power Supply, Rating is 9 A total with Special Application appliances 4 A total for. Regulated 24 DC appliance power, Outputs are power limited except for the battery charger.
4100ES Addressable Fire Detection and Control Basic Panel Modules and Accessories See module information sections for product that is UL or ULC listed and additional listing information This product has been listed by the California State Fire Marshal CSFM pursuant to Section 13144 1 of the California Health and Safety Code See CSFM Listing 7165 0026 251 4100ES for allowable values and