E340 BOILER CONTROL INSTALLATION MANUAL

E340 Boiler Control Installation Manual-Free PDF

  • Date:26 Apr 2020
  • Views:13
  • Downloads:0
  • Pages:16
  • Size:510.07 KB

Share Pdf : E340 Boiler Control Installation Manual

Download and Preview : E340 Boiler Control Installation Manual


Report CopyRight/DMCA Form For : E340 Boiler Control Installation Manual


Transcription:

ANALOG OUTPUTS,2 Analog outputs 4 20 mA signal 8 bit resolution. Maximum connected load 750 ohms,ANALOG INPUTS, 3 Pressure Inputs 1 5 VDC input control signal 12 bit resolution. 2 Temperature Inputs 1 000 0qC 12 bit resolution,COMMUNICATIONS. Protocol is Fireye half duplex DF1 or MODBUS, EIA standard RS485 serial link using 22 gauge twisted shielded pair wire. Maximum number of addressable controllers per communication link 255. BATTERY BACKUP, Lithium battery with expected life of 5 years 77qF 25qC.
Maintain RAM memory for 1 year 77qF 25qC without power. POWER REQUIREMENTS,20 Watts All relays energized,STORAGE TEMPERATURE LIMITS. 40qF 40qC to 158qF 70qC,COMPONENT DIMENSIONS,CONTROL WITH COVER AND WIRING BASE 5 11. P N E343 WIRING BASE MOUNTING HOLES 2 7 16,48 KNOCKOUTS 5 1 4. 7 9 32 5 3 4,44 4 25 32,1 2 KNOCKOUT 1 3 16 17 4,1 1 16 390. 27 4 7 8 TYP,SENSOR SPECIFICATIONS,OIL GAS STEAM PRESSURE RANGES.
x 0 to 16s water column,x 0 to 32s water column,x 0 to 160s water column. x 1 0 PSI to 17 0 PSI,x 1 0 to 33 0 PSI,x 10 to 170 PSI. x 10 to 330 PSI,x 50 to 850 PSI,All Pressure Sensors are 3 wire sensors. Control signal 1 5 VDC,Accuracy r 1 full scale,TEMPERATURE RANGES. x 32qF to 750qF,x 0qC to 400qC,Reference resistance 1000 ohms 0qC.
Temperature coefficient 00385 qC,Accuracy r 2qF 1qC. ORDERING INFORMATION,PART NUMBER DESCRIPTION,CONTROL COMPONENTS. E340 Boiler Room Control Includes Chassis Keypad Display Module and Dust Cover. EP340 Programmer Module for E340 Boiler Room Control. EB342 Chassis for E340 Boiler Room Control, E343 Wiring Base for E340 Boiler Room Control surface mounted UL Listed. E344 Wiring Base for E340 Boiler Room Control cabinet mounted UL Recognized. E345 Keypad Display Module for E340 Boiler Room Control. 60 2223 Dust Cover,SOLID STATE SENSORS,PS348 1 Pressure Sensor Range 0 16s Water Column. PS348 2 Pressure Sensor Range 0 32s Water Column,PS348 3 Pressure Sensor Range 0 160s Water Column.
PS348 4 Pressure Sensor Range 1 17 psig,PS348 5 Pressure Sensor Range 1 33 psig. PS348 6 Pressure Sensor Range 10 170 psig,PS348 7 Pressure Sensor Range 10 330 psig. PS348 8 Pressure Sensor Range 50 850 psig, TS348 2 Temperature Sensor Range 32q 750qF 0q 400qC 2s Probe Length. TS348 4 Temperature Sensor Range 32q 750qF 0q 400qC 4s Probe Length. TS348 8 Temperature Sensor Range 32q 750qF 0q 400qC 8s Probe Length. E340 ORDERING INFORMATION,Mounting Screw,E340 consists of. EB342 Chassis,EB342 Keypad Display Module,60 2223 Dust Cover.
Mounting Screw,60 2223 Dust Cover, EP340 Programmer Module E345 Keypad Display Module. Wiring Base,E343 Surface Mounted,E344 Cabinet Mounted shown. SYSTEM INPUTS AND OUTPUTS,RELAY OUTPUTS, The E340 provides 4 digital outputs to perform the following functions. Operating Control output wired in series with existing external operating limits to operating. control circuit of the flame safeguard control Terminals L1 13 of FLAME MONITOR and. D Series Control,Rated at 5 amps 120 VAC,Normally Open NO isolated output. Safety Circuit wired in series with existing external running interlocks to running interlock. circuit of the flame safeguard control Terminals 3 P of FLAME MONITOR and. D Series Control,Rated at 5 amps 120 VAC,Normally open NO isolated output.
Marginal Alarm output relay Rated at 5 amps 24 VAC. Auxiliary Relay output Rated at 5 amps 24 VAC,DIGITAL INPUTS. The E340 provides 8 digital inputs to monitor the following inputs. Fuel selector switch for gas operation Rated at 120 VAC. Fuel selector switch for oil operation Rated at 120 VAC. Fuel selector switch for heavy oil operation Rated at 120 VAC. Status of Main Fuel Valve Rated at 120 VAC, Input to determine Lead Lag operation Dry Contact Only. Position of the Firing Rate Damper Motor Resistive input 0 135. Input to Initiate Setback Mode Dry Contact Only, Input to Override Setback Mode Time determined by user Momentary Dry Contact Only. ANALOG INPUTS, The E340 provides 5 analog inputs to monitor the following. INPUT PRESSURE SENSORS MARGINAL ALARMS ALARM LIMITS. 1 Gas Pressure High and Low,2 Oil Pressure High and Low.
3 Steam Pressure High and Low,INPUT DESCRIPTOR TEMPERATURE MARGINAL ALARMS. SENSOR OPTIONS ALARM LIMITS,4 PRIMARY Primary Water Temp High and Low. Standby Water Temp None,Stack Temp High Only,Outdoor Temp None. 5 AUXILIARY Oil Temp High and Low,Stack Temp High Only. Outdoor Temp None,Low marginal alarm only No low alarm limit.
ANALOG OUTPUTS, The E340 provides 2 analog outputs 4 20 mA to provide the following. Proportional control of the Firing Rate Damper Motor. Selectable Output Signal based on the value of one of the 5 analog inputs. WIRING CONNECTIONS, All wiring must beet local and National Electrical Codes The fish paper insulator covering the Left. Terminal block is provided to isolate its line voltage loads from the low voltage loads connected to. the Right Terminal Block and Sub miniature Terminal block Shaded area denotes line voltage con. TERMINAL LEFT TERMINAL BLOCK LINE VOLTAGE,50 Running Interlock FSG Control Relay Output. 51 Running Interlock FSG Control1 Relay Output,52 Operating Control FSG Control2 Relay Output. 53 Operating Control FSG Control2 Relay Output,54 L2 Neutral FSG Control3.
55 Main Fuel Valve FSG Control4 Digital Input,56 Fuel Selector Switch Hvy Oil Digital Input. 57 Fuel Selector Switch Oil Digital Input,58 Fuel Selector Switch Gas Digital Input. 1 Terminals 3 and P of Fireye FLAME MONITOR and D Series Flame Safeguard Controls. 2 Terminals, L1 and 13 of Fireye FLAME MONITOR and D Series Flame Safeguard Controls. 3 Terminal L2 of Fireye FLAME MONITOR and D Series Flame Safeguard Controls. 4 Terminal 7 of Fireye FLAME MONITOR and D Series Flame Safeguard Controls. TERMINAL RIGHT TERMINAL BLOCK LOW VOLTAGE,40 Earth Ground. 41 24 VAC Hot,42 24 VAC Common,43 Alarm Output Marginal and Alarm.
44 Auxiliary Relay Output,45 4 20 mA Analog Output Firing Rate Motor. 46 4 20 mA Analog Output Firing Rate Motor,47 4 20 mA Selectable Analog Output. 48 4 20 mA Selectable Analog Output,TERMINAL SUB MINIATURE BLOCK LOW VOLTAGE. 60 24 VDC Gas Pressure,61 Sensor Return Line Gas Pressure. 62 Gas Pressure Sensor,63 24 VDC Oil Pressure,64 Sensor Return Line Oil Pressure.
65 Oil Pressure Sensor,66 24 VDC Steam Pressure,67 Sensor Return Line Steam Pressure. 68 Steam Pressure Sensor, 69 Water Temperature or Outdoor Air Stack or standby Temp Sensor. Water Temperature or Outdoor Air Stack or standby Temp Return. Auxiliary Temperature Sensor for Oil Temp Stack Temp or Outdoor. 71 Air Temp, Auxiliary Temperature Return Line for Oil Temp Stack Temp or Out. 72 door Air Temp,73 Damper Motor Position Feedback. 74 Damper Motor Position Feedback,75 Forced Setback.
76 Return Line Digital Inputs,77 Lead Lag Selector. 78 Return Line Digital Inputs,79 Setback Override,80 RS 485 Remote Communication Line B. 81 RS 485 Remote Communication Line A,WIRING CONNECTIONS LEFT TERMINAL BLOCK. Safety Circuit Terminals 50 and 51, The Safety Circuit relay Terminals 50 and 51 is wired in the running interlock circuit of the Flame. Safeguard Control Terminals 3 and P of the FLAME MONITOR and D Series controls The safety. circuit relay is wired in series with any other running interlock circuit e g high and low water cut. off etc To help limit electrical noise frequencies the safety circuit relay should be the first circuit. wired in the running interlock circuit of the flame safeguard control Refer to diagram below See. SEQUENCE OF OPERATION HIGH AND LOW ALARM LIMITS section in Bulletin E 3401. WARNING An electro mechanical steam pressure or hot water high limit switch. MUST REMAIN in the running interlock circuit of the flame safeguard control. Operating Control Circuit Terminals 52 and 53, The Operating Control Terminals 52 and 53 is wired in the operating control circuit of the Flame.
Safeguard Control Terminals L1 and 13 of the FLAME MONITOR and D Series controls The. operating control is wired in series with any other operating control limit e g burner on off switch. The operating control should be the first circuit wired in the operating control circuit of the flame. safeguard control after the burner on off switch if applicable Terminals 52 and 53 should be. wired in the same location as the operating control would normally be found Refer to diagram. below See SEQUENCE OF OPERATION OPERATING CONTROL section in Bulletin E 3401. FLAME MONITOR E340,TERMINALS TERMINALS,P EXTERNAL 50. RUNNING E340,INTERLOCKS INTERNAL,13 OPERATING 52,120 VAC Neutral L2 Terminal 54. To insure proper voltage reference between the E340 and flame safeguard control Terminal 54 is. wired to the 120 VAC Neutral connection of the flame safeguard control Terminal L2 of the. FLAME MONITOR and D Series control,Main Fuel Valve Terminal 55. Terminal 55 is wired to the main fuel valve connection of the flame safeguard control Terminal 7 of. the FLAME MONITOR and D Series control,Fuel Selector Switch Terminals 56 57 and 58. The E340 has three line voltage inputs Terminals 56 57 and 58 to monitor the status of a fuel. selector switch that determines which pressure and temperature sensors the E340 control will moni. tor For example if the selector switch is in the position for Oil the E340 control will disregard the. high and low alarm limits for gas pressure, Note When Heavy Oil is selected both the Oil and Heavy Oil inputs must be made.
Note If the associated sensor is programmed as UNUSED the input is ignored. Note If fuel selection is not detected all inputs open E340 displays NONE for Fuel Selected the. E340 will remain at low fire,WIRING CONNECTIONS RIGHT TERMINAL BLOCK. Earth Ground Terminal 40, A good earth ground is essential in the proper operation of the E340 Control. Powering the Control 24 VAC Terminals 41 Hot and 42 Common. The E340 control is powered by 24 VAC connected to Terminals 41 Hot and 42 Common The. power requirements of the E340 control is 20 VA The alarm output Terminal 43 and the auxiliary. relay output Terminal 44 are internally connected to Terminal 41 so the total connected load to. Terminals 43 and 44 should be considered when determining the total VA rating of the control trans. former The additional load of the mod motor should also be taken into account if powered by the. same control transformer, CAUTION To insure proper operation a ZTAH Transient Voltage Surge Suppressor by. Power Integrity Corp Greensboro NC or equivalent should be installed. Alarm Output Terminal 43, The E340 has a low voltage output Terminal 43 internally connected to Terminal 41 to serve as a. marginal alarm pulsed output and lockout alarm maintained output if any of the marginal alarm. or lockout alarm limits are exceeded See SEQUENCE OF OPERATION HIGH AND LOW. ALARM LIMITS section in Bulletin E 3401,24 VAC HOT E340.
24 VAC COMMON,Auxiliary Relay Terminal 44, The E340 has a low voltage output relay Terminal 44 internally connected to Terminal 41 which. can be programmed to operate according to a time of day schedule See SEQUENCE OF OPERA. TION PROGRAM ON section in Bulletin E 3401,Firing Rate Damper Motor Terminals 45 and 46. The E340 provides a 4 20mA analog output Terminals 45 and 46 to control a firing rate damper. motor in response to system demand See SEQUENCE OF OPERATION MODULATING CON. TROL section in Bulletin E 3401 This analog output controls the firing rate motor after the flame. safeguard control releases the firing rate motor to automatic control Terminals 10 and 11 of the. FLAME MONITOR made, The E340 can directly control a firing rate damper motor that will accept a 4 20mA control input sig. nal or control an industry standard 135 ohm slide wire firing rate damper motor by using a 4 20mA. to 135 ohm transducer These transducers are commercially available from a number of vendors. Terminal 45 is the positive reference for the 4 20mA output signal and Terminal 46 is the negative. Selectable 4 20mA Analog Output Terminals 47 and 48. The E340 provides a 4 20mA analog output Terminals 47 and 48 which allows the user to select. one of the five pressure or temperature sensors or command rate output to provide a 4 20mA output. signal that is directly proportional to the value of the selected sensor Terminal 47 is the positive ref. erence for the 4 20mA output signal and Terminal 48 is the negative reference The chart recorder. or similar device connected to these outputs should not have a maximum impedance greater than 750. 24 VAC COMMON,EXTERNAL EXTERNAL,L1 RUNNING OPERATING. 24 VAC INTERLOCKS LIMITS,S2 X 50 40,S1 P 51 41,B M 53 43 ALARM.
6 L2 55 45,5 L1 56 46,13 11 57 47 SEE FIGURES,12 10 58 48 2 3 FOR WIRING. TO TERM 45 46,FLAME MONITOR E340,OIL LIGHT CHART,FUEL SELECTOR SWITCH. FIGURE 2 Wiring E340 and E100 to a 4 20mA Firing Rate Damper Motor. COM HI LOW AUTO,10 X 12 11,FLAME MONITOR,E340 45 46. FIGURE 3 Wiring E340 and E100 to 135 Slide Wire Firing Rate Damper Motor Using a 4 20mA to 135. Transducer,E340 TERMINALS,COM HI LOW AUTO,10 X 12 11 TRANDUCER. FLAME MONITOR,TERMINALS 4 20mA to 135 W,4 20mA to 135W Transducer is commer 1.
The safety circuit relay is wired in series with any other running interlock circuit e g high and low water cut off etc To help limit electrical noise frequencies the safety circuit relay should be the first circuit wired in the running interlock circuit of the flame safeguard control Refer to diagram below See