ACM8 Series UL Listed Sub Assembly Access Power

Acm8 Series Ul Listed Sub Assembly Access Power-Free PDF

  • Date:05 Aug 2020
  • Views:3
  • Downloads:0
  • Pages:8
  • Size:517.05 KB

Share Pdf : Acm8 Series Ul Listed Sub Assembly Access Power

Download and Preview : Acm8 Series Ul Listed Sub Assembly Access Power


Report CopyRight/DMCA Form For : Acm8 Series Ul Listed Sub Assembly Access Power


Transcription:

These units are UL Listed Sub Assembly multi output Access Power Controllers which converts one 1 12 to 24 volt. DC input into eight 8 independently controlled fused or PTC protected outputs These power outputs can be converted to. dry form C contacts fused models only Outputs are activated by an open collector sink or normally open NO dry. trigger input from an Access Control System Card Reader Keypad Push Button PIR etc The units will route power to a. variety of access control hardware devices including Mag Locks Electric Strikes Magnetic Door Holders etc Outputs will. operate in both Fail Safe and or Fail Secure modes Units are designed to be powered by one common power source which. will provide power for both the board operation and locking devices or two 2 totally independent power sources one. 1 providing power for board operation and the other for lock accessory power The FACP Interface enables Emergency. Egress Alarm Monitoring or may be used to trigger other auxiliary devices The fire alarm disconnect feature is. individually selectable for any or all of the eight 8 outputs. ACM8 ACM8CB Series Configuration Reference Chart, Altronix Number Fuse PTC Output Class 2 Rated Agency UL Listings and. Model of Protected Protected Ratings Power Listings File Numbers. Number Outputs Outputs Outputs Limited,SECURITY UL File BP6714. ACM8 8 x 2 5 amp UL Listed for Access Control,System Units UL 294. ACM8CB 8 x 2 amp x Signal Equipment Evaluated to CSA. Sub Assembly,Standard C22 2 No 205 M1983,Specifications. 12 to 24 volt DC operation setting not required, 0 5 amp 12volt 0 3 amp 24volt current consumption with all relays energized.
Power supply input options,a One 1 common power input board and lock power. b Two 2 isolated power inputs one 1 for board power and one 1 for lock hardware power. Eight 8 Access Control System trigger inputs,a Eight 8 normally open NO inputs. b Eight 8 open collector sink inputs,c Any combination of the above. Eight 8 independently controlled outputs, a Eight 8 Fail Safe and or Fail Secure power outputs. b Eight 8 dry form C 5 amp rated relay outputs,c Any combination of the above.
Eight 8 auxiliary power outputs unswitched,Output ratings. Fuses are rated 3 5 amp each,PTCs are rated 2 amp each. Main fuse is rated at 10 amp, Note Total output current is determined by the power supply not to exceed a maximum of 10 amp total. Red LEDs indicate outputs are triggered relays energized. Fire Alarm disconnect latching or non latching is individually selectable for any or all of the eight 8 outputs. Fire Alarm disconnect input options, a Normally open NO or normally closed NC dry contact input. b Polarity reversal input from FACP signaling circuit. FACP output relay form C contact rated 1 amp 28VDC not evaluated by UL. Green LED indicates when FACP disconnect is triggered. Removable terminal blocks facilitate ease of installation. Board Dimensions approximate 8 L x 4 5 W x 1 25 H,2 ACM8 CB Sub Assembly.
Installation Instructions, Wiring methods shall be in accordance with the National Electrical Code NFPA 70 NFPA 72 ANSI and with all local. codes and authorities having jurisdiction Product is intended for indoor use only and should be installed. by qualified personnel, 1 Refer to Sub Assembly Installation Instruction for mounting Rev MS042511. Carefully review, Typical Application Diagram pg 4 Terminal Identification Table pg 5. LED Diagnostics pg 5 Hook up Diagrams pg 6,2 Power supply input. The units can be powered with one 1 power supply which will provide power for both board operation and. the locking devices or two 2 separate power supplies one 1 to provide power for the board operation and. the other to provide power for the locking devices and or access control hardware. Note The input power can be 12 to 24 volts DC 5 amp 12 volt 3 amp 24 volt current consumption. with all relays energized,a Single power supply input.
If the unit and the locking devices are to be powered using a single power supply connect the output. 12 to 24 volts DC to the terminals marked Control,b Dual power supply inputs Fig 1 pg 4. When the use of two power supplies is desired jumpers J1 and J2 located to the left of the power control. terminals must be cut Connect power for the unit to the terminals marked Control and connect power for the. locking devices to the terminals marked Power, Note When using DC power supplies polarity must be observed When using AC power supplies polarity. need not be observed, Note For UL compliance the power supplies must be UL Listed for Access Control Systems and accessories. 3 Output options Fig 1 pg 4, The ACM8 will provide either eight 8 switched power outputs eight 8 dry form C outputs or. any combination of of both switched power and form C outputs plus eight 8 unswitched auxiliary power outputs. The ACM8CB will provide eight 8 switched power outputs or eight 8 unswitched auxiliary power outputs. a Switched Power outputs, Connect the negative input of the device being powered to the terminal marked COM For Fail Safe operation.
connect the positive input of the device being powered to the terminal marked NC For Fail Secure operation. connect the positive input of the device being powered to the terminal marked NO. b Form C outputs, When form C outputs are desired the corresponding output fuse 1 8 must be removed Connect negative of. the power supply directly to the locking device Connect the positive of the power supply to the terminal marked. C For Fail Safe operation connect the positive of the device being powered to the terminal marked NC For. Fail Secure operation connect the positive of the device being powered to the terminal marked NO. c Auxiliary Power outputs unswitched, Connect positive input of the device being powered to the terminal marked C and the negative of the device. being powered to the terminal marked COM Output can be used to provide power for card readers keypads etc. 4 Input trigger options Fig 1 pg 4,a Normally Open NO input trigger. Inputs 1 8 are activated by normally open or open collector sink inputs. Connect devices card readers keypads request to exit buttons etc to terminals marked IN and GND. b Open Collector Sink inputs, Connect the access control panel open collector sink positive to the terminal marked IN and the. negative to the terminal marked GND, 5 Fire Alarm Interface options Figs 3 through 7 pg 6.
A normally closed NC normally open NO input or polarity reversal input from FACP signaling circuit will. trigger selected outputs To enable FACP Disconnect for an output open the corresponding switch SW1 SW8. To disable FACP disconnect for an output close the corresponding switch SW1 SW8. a Normally Open NO input, For non latching hook up Fig 4 pg 6 For latching hook up Fig 5 pg 6. b Normally Closed NC input, For non latching hook up Fig 6 pg 6 For latching hook up Fig 7 pg 6. ACM8 CB Sub Assembly 3,c FACP Signaling Circuit input trigger. Connect the positive and negative from the FACP signaling circuit output to the terminals marked INP. Connect the FACP EOL to the terminals marked RET polarity is referenced in an alarm condition. Jumper J3 must be cut Fig 3 pg 6,6 FACP Dry form C output Fig 1a pg 4. Connect desired device to be triggered by the unit s dry contact output to the terminals marked NO and C. FACP for normally open output or the terminals marked NC and C FACP for normally closed output. Note This product is a UL Listed Sub Assembly for use with Altronix UL Listed power supplies as indicated in the. installation manuals for the power supply,Typical Application Diagram.
ACCESS CONTROL NORMALLY OPEN KEYPAD,PANEL N O DOOR. RELEASING DEVICE FACP FACP Dry,OUTPUT Fire Alarm Output. RELAY NO Control Panel,Fire Alarm System Power Supply Unit. Also suitable for use as a,Access Control System Unit Subassembly. Refer to Installation Instructions IN GND IN GND IN GND IN GND IN GND IN GND IN GND IN GND TRG. IIACM8 REV 092503,1 2 3 4 5 6 7 8,F1 F2 F3 F4 F5 F6 F7 F8.
3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V. FACP Interface Enabled,FACP Interface Disabled,LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8. Power Control, NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM NC C NO COM. OUTPUT 1 OUTPUT 2 OUTPUT 3 OUTPUT 4 OUTPUT 5 OUTPUT 6 OUTPUT 7 OUTPUT 8. UL Listed AC or DC AC or DC,POWER SUPPLY POWER POWER. ELECTRIC For this application SUPPLY SUPPLY,STRIKE optional req d. corresponding,fuse F8 must be,ELECTROMAGNETIC removed MAG.
DOOR HOLDERS LOCK,ACM8 ACM8CB,F1 F2 F1 F2,WARNING To reduce the risk of fire or. electric shock do not expose the unit to,3 5A 250V 3 5A 250V. 2A 250V 2A 250V,rain or moisture,Replace fuses ACM8 ACM8E models only. with the same type and rating 3 5 amp 250V,LED1 LED2 LED1 LED2. 4 ACM8 CB Sub Assembly,LED Diagnostics,ACM8 ACM8CB Access Power Controller.
LED ON OFF, LED 1 LED 8 Red Output relay s energized Output relay s de energized. Trg Green FACP input triggered alarm condition FACP normal non alarm condition. Terminal Identification Tables,ACM8 ACM8CB Access Power Controller. Terminal Legend Function Description, Power 12VDC or 24VDC input from power supply board. These terminals can be connected to a separate UL Listed power supply to. Control provide isolated operating power for the ACM8 ACM8CB. jumpers J1and J2 must be removed, From normally open and or open collector sink trigger inputs. INPUT 1 INPUT 8,request to exit buttons exit pir s etc.
12 to 24 volts AC DC trigger controlled outputs,Fail Safe NC positive COM Negative. Fail Secure NO positive COM Negative,OUTPUT 1 OUTPUT 8. Auxiliary output C positive COM Negative,NC C NO COM. When using AC power supplies polarity need not be observed. NC C NO become form C 5 amp 24VAC VDC rated dry outputs when fuses are. removed ACM8 Contacts shown in a non triggered state. FACP INTERFACE Fire Alarm Interface trigger input from FACP Trigger inputs can be normally open. T INPUT normally closed from an FACP output circuit Fig 3 through 7 pg 6. FACP INTERFACE Form C relay contact rated 1 amp 28VDC for alarm reporting. NC C NO This output has not been evaluated by UL,ACM8 CB Sub Assembly 5. Hook up Diagrams, Fig 2 Optional hook up using two 2 isolated Fig 3 Polarity reversal input from FACP signaling circuit.
power supply inputs output polarity is referenced in alarm condition. CUT JUMPERS JUMPER J3,OUTPUT EOL,ISOLATED POWER INPUT TRG. J1 12 OR 24 VAC OR VDC,ACM8 POWER,ISOLATED POWER INPUT. 12 OR 24 VAC OR VDC,LOCK POWER, Fig 4 Normally Open Non Latching FACP Fig 5 Normally Open FACP Latching trigger input. trigger input with reset,This output has not been evaluated by UL. N O TRIGGER, Fig 6 Normally Closed Non Latching FACP Fig 7 Normally Closed Latching FACP trigger input.
trigger input with reset,This output has not been evaluated by UL. N C DRY N C RESET,TRG SWITCH,N C TRIGGER,JUMPER INPUT. 6 ACM8 CB Sub Assembly,ACM8 CB Sub Assembly 7, Altronix is not responsible for any typographical errors. 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056. web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A. IIACM8 ACM8CB series D28K MEMBER,8 ACM8 CB Sub Assembly. SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 FACP Interface Enabled FACP Interface Disabled SW1 SW8 ACM8 ACM8CB FACP Dry Form C NO C NC FACP LED1 F1 LED2 F2 3 5A 250V 3 5A 250V SW1 SW2 LED1 F1 LED2 F2 2A 250V 2A 250V SW1 SW2 Fire Alarm System Power Supply Unit Also suitable for use as a Access Control System Unit Subassembly 39BA Refer to Installation Instructions IIACM8 REV 092503 Fig 1 Fig 1a