4603 9101 LCD Annunciator installation instructions. Specifications, Table 1 Power requirements and environmental limitations. Voltage 24VDC Power Supply 24VDC Nominal, Current Maximum Current Draw with LCD Backlight OFF at 24VDC 65mA. Maximum Current Draw with LCD Backlight ON at 24VDC 110mA. Maximum Current Draw with LCD Backlight ON and Piezo ON at 18VDC 140mA. Temperature Operating Range 32 F to 120 F 0 C to 49 C. Humidity The equipment operates normally under non condensing humidity conditions up to 93. relative humidity at 100 F 38 C, All circuits are power limited if the operating power and communications are provided by a. 4020 control unit or by a system with the 4100 4120 6050 power limited option. If the interconnected control unit is not used to provide operating power to the annunciator. use a regulated UL listed 24VDC power supply for fire protective signaling. At least an 18 AWG twisted wire is required If twisted shielded pair wire is used ground the. shield at the main panel, Center the conduit entry a minimum of 2 in 70mm from the front of the box. Ensure the number of annunciators in a 4100ES 4100U 4100 fire alarm system does not. Do not use the 4603 9101 LCD Annunciator when the 4100ES 4100U 4100 control panel. is configured for proprietary receiving service, In accordance with NFPA 70 Article 250 provide a dedicated earth ground connection to the.
back box for transient suppression,Flush mount 4603 9101 LCD annunciators. In masonry walls use a Steel City GW 635 G 3 in 89mm deep masonry box or an. equivalent box, In plasterboard walls use a RACO 590 3 in 89mm deep gangable switch box with. conduit entry or an equivalent box,Surface mount 4603 9101 LCD annunciators. Use a 2975 9206 box 2 in 70mm deep or a 2975 9217 box 1 in 44 45 mm deep. Installing the Complete the following steps to install the 4603 9101 LCD annunciator Refer to the Field Wiring. 4603 9101 LCD Diagram manual 841 731 for additional details. Annunciator 1 Terminate the annunciator s COMM and power lines as shown in Figure 2. 4 3 2 1 6 5 4 3 2 1,24V 24C COMM COMM SHIELD, TB2 1 to 24C of next Annunciator TB1 1 SHIELD to next Annunciator. TB2 2 from 24C of FACU power TB1 2 SHIELD from FACU or previous Annunciator. supply or previous Annunciator,TB1 3 COMM to next Annunciator.
TB2 3 to 24V of next Annunciator,TB1 4 COMM from FACU or previous Annunciator. TB2 4 from 24V of FACU power, supply or previous Annunciator TB1 5 COMM to next Annunciator. TB1 6 COMM from FACU or previous Annunciator,Figure 2 Terminating the COMM and power lines. 2 Connect the ground harness 733 936 to earth ground. Note To prevent Electrostatic Discharge ESD use a wrist strap assembly that connects to ground Ensure. the power is OFF before installing or servicing the annunciator Terminate the annunciator s power and. communication lines on the electronics assembly using the information in Figure 2. Continued on the next page, 4603 9101 LCD Annunciator installation instructions. Installing the,4603 9101 LCD 24C 24VDC,Annunciator.
TB1 GROUND HARNESS, Figure 3 Power and RUI communicating Wiring to TB1 and TB2. 3 Using switch SW2 see Figure 4 set the annunciator s address and baud rate in accordance. with Table 2 Switches SW2 1 LSB through SW2 7 MSB set the annunciator s address. and switch SW2 8 sets the annunciator s baud rate, SW2 8 OFF or OPEN 1200 Baud used to take the unit off line. SW2 8 ON or CLOSED 9600 Baud,Position 3 shown in,OFF position. Note DIP switch SW2,is located at the bottom of the. electronics assembly Example shows,ON Baud 9600,1 2 3 4 5 6 7 8.
Figure 4 DIP Switch SW2, 4 Using the two slotted screws provided mount the annunciator in the back box see Figure 5. Note When installing the,LCD assembly it is,important to use the Label pocket. holes specified in,Contrast adjustment,Slotted screws part no 412 059. Figure 5 LCD assembly, 5 Label the user defined labels with the appropriate designation Pull the top of the label pocket. forward and insert the user defined labels, 6 Using the four oval head screws provided mount the trim plate to the back box see Figure 6.
Two slotted screws,part no 412 059,LCD assembly,Four oval head screws. Part No 411 702 Trim plate, Figure 6 Expanded view of 4603 9101 LCD Annunciator. The trim plate covers a hole in the keyboard which provides access to the display s. viewing angle potentiometer, 4603 9101 LCD Annunciator installation instructions. Address chart,Table 2 Address chart, SW2 1 LSB SW2 2 SW2 3 SW2 4 SW2 5 SW2 6 SW2 7 MSB ADDRESS. OFF ON ON ON ON ON ON ADDRESS 1,ON OFF ON ON ON ON ON ADDRESS 2.
OFF OFF ON ON ON ON ON ADDRESS 3,ON ON OFF ON ON ON ON ADDRESS 4. OFF ON OFF ON ON ON ON ADDRESS 5,ON OFF OFF ON ON ON ON ADDRESS 6. OFF OFF OFF ON ON ON ON ADDRESS 7,ON ON ON OFF ON ON ON ADDRESS 8. OFF ON ON OFF ON ON ON ADDRESS 9,ON OFF ON OFF ON ON ON ADDRESS 10. OFF OFF ON OFF ON ON ON ADDRESS 11,ON ON OFF OFF ON ON ON ADDRESS 12.
OFF ON OFF OFF ON ON ON ADDRESS 13,ON OFF OFF OFF ON ON ON ADDRESS 14. OFF OFF OFF OFF ON ON ON ADDRESS 15,ON ON ON ON OFF ON ON ADDRESS 16. OFF ON ON ON OFF ON ON ADDRESS 17,ON OFF ON ON OFF ON ON ADDRESS 18. OFF OFF ON ON OFF ON ON ADDRESS 19,ON ON OFF ON OFF ON ON ADDRESS 20. OFF ON OFF ON OFF ON ON ADDRESS 21,ON OFF OFF ON OFF ON ON ADDRESS 22.
OFF OFF OFF ON OFF ON ON ADDRESS 23,ON ON ON OFF OFF ON ON ADDRESS 24. OFF ON ON OFF OFF ON ON ADDRESS 25,ON OFF ON OFF OFF ON ON ADDRESS 26. OFF OFF ON OFF OFF ON ON ADDRESS 27,ON ON OFF OFF OFF ON ON ADDRESS 28. OFF ON OFF OFF OFF ON ON ADDRESS 29,ON OFF OFF OFF OFF ON ON ADDRESS 30. OFF OFF OFF OFF OFF ON ON ADDRESS 31,ON ON ON ON ON OFF ON ADDRESS 32.
OFF ON ON ON ON OFF ON ADDRESS 33,ON OFF ON ON ON OFF ON ADDRESS 34. OFF OFF ON ON ON OFF ON ADDRESS 35,ON ON OFF ON ON OFF ON ADDRESS 36. OFF ON OFF ON ON OFF ON ADDRESS 37,ON OFF OFF ON ON OFF ON ADDRESS 38. OFF OFF OFF ON ON OFF ON ADDRESS 39,ON ON ON OFF ON OFF ON ADDRESS 40. OFF ON ON OFF ON OFF ON ADDRESS 41,ON OFF ON OFF ON OFF ON ADDRESS 42.
OFF OFF ON OFF ON OFF ON ADDRESS 43,ON ON OFF OFF ON OFF ON ADDRESS 44. OFF ON OFF OFF ON OFF ON ADDRESS 45,ON OFF OFF OFF ON OFF ON ADDRESS 46. OFF OFF OFF OFF ON OFF ON ADDRESS 47,ON ON ON ON OFF OFF ON ADDRESS 48. OFF ON ON ON OFF OFF ON ADDRESS 49,ON OFF ON ON OFF OFF ON ADDRESS 50. OFF OFF ON ON OFF OFF ON ADDRESS 51,ON ON OFF ON OFF OFF ON ADDRESS 52.
OFF ON OFF ON OFF OFF ON ADDRESS 53,ON OFF OFF ON OFF OFF ON ADDRESS 54. OFF OFF OFF ON OFF OFF ON ADDRESS 55,ON ON ON OFF OFF OFF ON ADDRESS 56. OFF ON ON OFF OFF OFF ON ADDRESS 57,ON OFF ON OFF OFF OFF ON ADDRESS 58. OFF OFF ON OFF OFF OFF ON ADDRESS 59,ON ON OFF OFF OFF OFF ON ADDRESS 60. OFF ON OFF OFF OFF OFF ON ADDRESS 61,ON OFF OFF OFF OFF OFF ON ADDRESS 62.
OFF OFF OFF OFF OFF OFF ON ADDRESS 63,ON ON ON ON ON ON OFF ADDRESS 64. Continued on next page, 4603 9101 LCD Annunciator installation instructions. Table 2 Address chart Continued, SW2 1 LSB SW2 2 SW2 3 SW2 4 SW2 5 SW2 6 SW2 7 MSB ADDRESS. OFF ON ON ON ON ON OFF ADDRESS 65,ON OFF ON ON ON ON OFF ADDRESS 66. OFF OFF ON ON ON ON OFF ADDRESS 67,ON ON OFF ON ON ON OFF ADDRESS 68.
OFF ON OFF ON ON ON OFF ADDRESS 69,ON OFF OFF ON ON ON OFF ADDRESS 70. OFF OFF OFF ON ON ON OFF ADDRESS 71,ON ON ON OFF ON ON OFF ADDRESS 72. OFF ON ON OFF ON ON OFF ADDRESS 73,ON OFF ON OFF ON ON OFF ADDRESS 74. OFF OFF ON OFF ON ON OFF ADDRESS 75,ON ON OFF OFF ON ON OFF ADDRESS 76. OFF ON OFF OFF ON ON OFF ADDRESS 77,ON OFF OFF OFF ON ON OFF ADDRESS 78.
OFF OFF OFF OFF ON ON OFF ADDRESS 79,ON ON ON ON OFF ON OFF ADDRESS 80. OFF ON ON ON OFF ON OFF ADDRESS 81,ON OFF ON ON OFF ON OFF ADDRESS 82. OFF OFF ON ON OFF ON OFF ADDRESS 83,ON ON OFF ON OFF ON OFF ADDRESS 84. OFF ON OFF ON OFF ON OFF ADDRESS 85,ON OFF OFF ON OFF ON OFF ADDRESS 86. OFF OFF OFF ON OFF ON OFF ADDRESS 87,ON ON ON OFF OFF ON OFF ADDRESS 88.
OFF ON ON OFF OFF ON OFF ADDRESS 89,ON OFF ON OFF OFF ON OFF ADDRESS 90. OFF OFF ON OFF OFF ON OFF ADDRESS 91,ON ON OFF OFF OFF ON OFF ADDRESS 92. OFF ON OFF OFF OFF ON OFF ADDRESS 93,ON OFF OFF OFF OFF ON OFF ADDRESS 94. OFF OFF OFF OFF OFF ON OFF ADDRESS 95,ON ON ON ON ON OFF OFF ADDRESS 96. OFF ON ON ON ON OFF OFF ADDRESS 97,ON OFF ON ON ON OFF OFF ADDRESS 98.
OFF OFF ON ON ON OFF OFF ADDRESS 99,ON ON OFF ON ON OFF OFF ADDRESS 100. OFF ON OFF ON ON OFF OFF ADDRESS 101,ON OFF OFF ON ON OFF OFF ADDRESS 102. OFF OFF OFF ON ON OFF OFF ADDRESS 103,ON ON ON OFF ON OFF OFF ADDRESS 104. OFF ON ON OFF ON OFF OFF ADDRESS 105,ON OFF ON OFF ON OFF OFF ADDRESS 106. OFF OFF ON OFF ON OFF OFF ADDRESS 107,ON ON OFF OFF ON OFF OFF ADDRESS 108.
OFF ON OFF OFF ON OFF OFF ADDRESS 109,ON OFF OFF OFF ON OFF OFF ADDRESS 110. OFF OFF OFF OFF ON OFF OFF ADDRESS 111,ON ON ON ON OFF OFF OFF ADDRESS 112. OFF ON ON ON OFF OFF OFF ADDRESS 113,ON OFF ON ON OFF OFF OFF ADDRESS 114. OFF OFF ON ON OFF OFF OFF ADDRESS 115,ON ON OFF ON OFF OFF OFF ADDRESS 116. OFF ON OFF ON OFF OFF OFF ADDRESS 117,ON OFF OFF ON OFF OFF OFF ADDRESS 118.
OFF OFF OFF ON OFF OFF OFF ADDRESS 119, 4603 9101 LCD Annunciator installation instructions. General wiring Use copper conductors for all wiring. precautions Do not exceed the maximum lengths specified in Table 3 through Table 6. If shielding is used, Ensure the metallic continuity of the shield is maintained throughout the entire length of. Ensure the entire length of the cable has a resistance greater than 1 X 106 ohms to Earth. Ensure the shield connects to a SHIELD terminal at each annunciator and is terminated. only at the main panel,Ensure underground wiring is free of water. Do not run wires through elevator shafts, Wire runs in plenums must be in a conduit unless they are rated for plenum use. Splicing is permitted in the following situations, All connections are soldered rosin core solder crimped in metal sleeves or encapsulated.
with an epoxy resin, When using solder or crimped metal sleeves ensure the junction is insulated using a high. grade electrical tape that equals the quality of the original insulating jacket. The shield s continuity is maintained throughout the cable s length. Do not run other wiring in the same conduit as system wiring. Specific wiring Ensure that 24V power wiring is power limited. precautions 4603 9101 LCD Annunciator wiring that leaves the building either above or below ground. requires overvoltage suppression at both ends, Communication and power wiring must use a UL497B listed suppressor that is compatible. with a maximum circuit voltage of at least 32VDC and a current rating high enough for the. The maximum wire length is 2500 feet 762 meters, Use the Simplex suppressor model number 2081 9027 200 mA maximum or 2081 9028. 5 amp maximum isolated loop circuit protector, For underground wiring select the appropriate isolated loop circuit protector Run the. circuit wiring in a separate parallel wiring trough to separate it from any commercial power. distribution wiring, For overhead wiring select the appropriate isolated loop circuit protector The wiring is.
limited to one contiguous property and the total wire length must not exceed 2500 feet 762. meters Run the circuit wiring on separate poles to separate it from any poles supporting. commercial power distribution wiring Run the circuit wiring in parallel with direct relation. to the commercial power distribution The separation is a minimum distance whichever is. greater of 100 feet 30 48 meters or the maximum span between any two adjacent poles of. either the system s circuit or the commercial power distribution circuit. For more information about maximum wire lengths when using circuit protectors see Tables. 3 through 6, Communication wiring is supervised and power limited. For more information about wiring the 4603 9101 LCD Annunciator refer to the following. 4100 Field Wiring Diagram 841 731, 4100ES Fire Alarm System Installation Guide 574 848. 4100 Fire Alarm System Contractor Installation Instructions 574 019. 4020 Fire Alarm System Contractor Installation Instructions 574 061. 4603 9101 LCD Annunciator installation instructions. 4100ES 4100U When wiring a 4100ES 4100U 4100 4020 FACU to an LCD Annunciator for serial. 4100 4020 to communication, LCD The annunciator terminal blocks accommodate 12 18 AWG wire. Annunciator, wiring for serial When used with audio riser wiring telephone wiring or 4120 Network wiring the. communication communication lines must be twisted shielded pair. Parallel configurations are acceptable where the total distance of all series and parallel runs. do not exceed the maximum distances specified in Table 5 and Table 6. The maximum operating conditions for the Communication Line is 32VDC 130mA. 4100ES 4100U When wiring a 4100ES 4100U 4100 4020 FACU to an LCD Annunciator for operating power. 4100 4020 to The annunciator terminal blocks accommodate 12 18 AWG wire see Table 3 and Table 4. Each 4603 9101 LCD Annunciator uses,Annunciator,wiring for 110 mA 0 110 A in standby.
operating power An alarm current of 140 mA, A battery standby current backlight and piezo off is 65 mA. Ensure the operating power is provided by the system power supply. Tyco Simplex and the product names listed in this material are marks and or registered marks Unauthorized use is strictly prohibited 579 979 Rev E Introduction The 4603 9101 Liquid Crystal Display LCD annunc iator is for use with 4100ES 4100U 4100 4120 4020 Fire Alarm Control Unit FACUs and 4100 4120 Universal Transponders Only the