l Do not install detectors in areas where there is likely to be steam in hospital patient rooms with vaporizers near. shower rooms above large sinks etc, l Do not install detectors above ashtrays in elevator lobbies. l Wall mounted detectors should be located 4 to 12 inches 1O 30 5 cm from the ceiling to detector head. l Protect all detector heads during construction to avoid infiltration of construction debris. MAINTENANCE, The minimal requirement for detector maintenance should consist of cleaning surface dust by using a vacuum. cleaner Cleaning programs should comply with NFPA and local environments Cleaning of the internal chamber. should be done by Simplex technical representative only. TEST EQUIPMENT AVAILABLE,2098 9822 553 394 Extendable Smoke Generator. 2098 9809 553 533 Sensitivity Tester, 2098 9814 553 536 Test and Removal Tool for use with 2098 9201 9202 9203 9576. 2098 9815 553 553 Test and Removal Tool Holder for use with 553 536 553574. 553 574 Test and Removal Tool for use with 2098 9208. Before testing disconnect city release devices and extinguish systems Notify all appropriate personnel of test The. preferred test is with smoke using a 553 394 Extendable Smoke Generator If this method is not acceptable or. practical a functional test can be performed by using a Test and Removal Tool To test the detector place the test. tool around the detector body This will alarm the detector To clear the detector remove the test tool and reset the. fire alarm panel,SPECIFICATIONS 1 SMOKE DETECTOR DATA.
Detector 2098 9576 2098 9201 2098 9202 2098 9203 t2098 9208. Type of Detector Ionization Photoelectric Photoelectric Photoelectric Photoelectric. Working Voltage 15 36 3 VDC 15 36 3 VDC 15 36 3 VDC 15 36 3 VDC 15 32 VDC. 17 7 33 0 VDC 17 7 33 0 VDC 17 7 33 0 VDC 17 7 33 0 VDC 17 7 33 0 VDC. Filtered DC Filtered DC Filtered DC Filtered DC Filtered DC t. Voltage Waveform 18V Ripple Max 18V Ripple Max 18V Ripple Max 18V Ripple Max 18V Ripple Max. Max Alarm Current 86 mA 86 mA 86 mA 86 mA 86 mA,Surge Current 200 uA 200 uA 200 uA 200 uA 200 uA. Standby Current 40 uA 40 uA I, Heat Element Rating N A N A 1 135 Degrees F 1 N A N A. Compatibility 2098 9576 2098 9201 2098 9202 2098 9203 2098 9208. Identifier,Magnet or Magnet or 5yg y,Test Procedure I 553 536 y5y o 553 536 y5tj n r. Max Qty Per See Table 4 See Table 4 See Table 4 See Table 4 See Table 4. Initiating Circuit, t CAUTION Do not use the 2098 9208 detector with the 2098 9734 power pack The 2098 9208 does not. operate from a full wave rectified unfiltered DC power source. When using 2098 9536 four wire base full wave rectified DC can be used. l Compatibility identifier is the PID model number found on the panel or module and detector base. Technical Manuals Online http www tech man com,I BASE 3 l 2 OCTAGONAL.
BOX MOUNTING,1 4 OCTAGONAL 1 4 SQUARE,Yes Yes Yes,Yes Yes Yes. Yes Yes No,4 10 16 CM Octagonal,Outlet Box,Not Furnished by Simplex. Wire per NEC Article 370,2098 9211 2098 9536,2098 9637 2098 9201 Detector Detector. Base 2098 9203 2098 9202 2098 9208,TABLE 3 TABLE 4. MAX QTY OF,INITIATING BASES PER,CIRCUITS DEHTEEACoTsoR INITIATING CIRCUIT.
PID 2098 9211,SeeTable kd Note5,2098qr9211,2120 7012 2098 9201 with. 2120 7013 2098 9202 2098 9738 See Aotel,2120 7014 2098 9203 209 827. 2120 7015 2098 9208,2120 7019 2098059576 2098 9637 SeeTable md Note5. 2120 7023 2098 637,2120 7024 with,2098 9738 See Aote 1. 2120 7032 209 827,2120 7033 Notes, 4002 5001 1 Relay operation cannot be guaranteed unless it is the only device on that zone.
2 Panel compatibility identification marker is the model number of the module or panel. 4002 5002 3 Detector compatibility identification marker is the model number found on the detector label. 4002 5003 4 For detailed interconnection data see wiring diagrams in Document 841 687. 5 Exceptions for the maximum quantity of 30 bases per initiating circuit are as follows. lnitiatino Circuit Qtv of Bases,4020 0305 2120 0523 20. 4020 7003 2120 0527 20,2120 7011 18,4100 5001 2120 7022 18. 4100 5002 2120 7805 25,2120 7806 25,4100 5011 4001 9403 18. 4100 5012 4001 9404 18,4001 9813 18,Technical Manuals Online http www tech man com. Red labeled detector heads MUST only,be used with red labeled bases Use in any other.
base will result in a non functioning detector,These heads include. Heads Head,2098 9201 098 9208,2098 9202 ea,P Wire 4 Wire. Base 2098 9637 Base 2098 9536, Install the bases in this instruction in accordance with applicable NFPA standards local codes and the. authorities having jurisdiction Failure to follow these instructions may result in failure of the detector to initiate. an alarm condition Simplex is not responsible for detectors that have been improperly installed tested or. maintained, CONNECT WIRING TO TERMINALS AS SHOWN DO NOT LOOP WIRE UNDER TERMINALS BREAK WIRE. RUN TO PROVIDE SUPERVISION OF CONNECTIONS,Technical Manuals Online http www tech man com.
Base 2098 9536 Base 2098 9536 Base 2098 9536,Head 2098 9201 Head 2098 9201 Head 2098 9201. 2098 9202 2098 9202 2098 9202 24 VDC,2098 9203 2098 9203 2098 9203 EOL Relay. 2098 9208 2098 9208 2098 9208 2098 9735,2098 9576 2098 576 2098 9576 2098 9739. Ll Ll Ll Elk,source i l,See Note 3,Blk 1 Note,Note I 1 5. Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring DO NOT USE RELAY if LED is. 3 DO NOT USE REMOTE LED when relay 2098 9737 is used. 4 Aux alarm contacts form C each rated 1A 24VDC or 115VAC resistive. 5 Aux alarm contacts two form C each rated 3A 24VDC or 115VAC resistive. 6 Refer to wiring diagrams provided with system panel for proper end of line resistor value. 2098 9536 BASE CONNECTIONS,Fire Alarm see see RE,Control Note 2 Note2.
Base 2098 9637 Base 2098 9637, Panel Head 2098 9201 Head 2098 9201 Head 2098 9201. 2120 2098 9202 2098 9202 2098 9202,4001 4002 2098 9203 2098 9203 2098 9203. 4020 or4100 2098 9208 2098 9208 2098 9208,2098qr9576 2096576 2092576. Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 It is recommended that the primary l and the backup 2 lines be in separate wire runs and in compliance with local. requirements, 2098 9637 BASE CONNECTIONS FOR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. Technical Manuals Online http www tech man com,Listed Note.
Fire Alarm,Panel Head 2098 9201 Head 20989201,Head 20989201. 2120 2098 9202 2098 9202 2098 9202,4001 4002 2098 9203 2098 9203 2098 9203. 1020 or4100 2098 9208 2098 9208 2098 9208,2098qr9578 209E9576 2098qr9576. Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 20989808 is polarized observe color coded wiring. 3 Refer to wiring diagrams provided with system panel for proper end of line resistor value. 2098 9637 BASE CONNECTIONS FOR STYLE B FORMERLY CLASS B INITIATE CIRCUIT. I Primarv 1 I,I I See Note,Fire Alarm Aux Relay Contacts. Control Rated 1 A 1124VDC,Panel Or 115VAC Resistive.
2120 Base 2098 9637 2098 9738,4001 4002 Relay Module 2098 9738 Relay Module. 4020 or4100 Head 20989201 See Note 3, Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 When wiring relay to base remove resistor black wire from base terminal 53 Wire only one base relay per initiate circuit. 4 For Style D formerly Class A initiate circuit wire per dotted lines and do not use EOL resistor If Style B formerly Class. B initiate circuit refer to wiring diagrams provided with system panel for proper EOL resistor value. 5 For Style D formerly Class A wiring it is recommended that the primary l and the backup 2 lines be in separate wire. runs and in compliance with local requirements,20989637 WITH 20989738. BASE AND RELAY CONNECTIONS FOR STYLE B FORMERLY CLASS B OR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. Technical Manuals Online http www tech man com,I Primary 1. Aux Relay Contacts,Fire Alarm Rated 1 A I 24VDC,Control Or 115VAC Resistive.
2120 Base 2098 9211 2098 9738,4001 4002 Blk Relay Module 2098 9738 Relay Module. 020 or 4100 Head 2098 9201 See Note 3, Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 When wiring relay to base cut JW Wire only one base relay per initiate circuit. 4 For Style D formerly Class A initiate circuit wire per dotted lines and do not use EOL resistor If Style B formerly Class. B initiate circuit refer to wiring diagrams provided with system panel for proper EOL resistor value. 5 For Style D formerly Class A wiring it is recommended that the primary l and the backup 2 lines be in separate wire. runs and in compliance with local requirements,2098 9211 WITH 2098 9738. BASE AND RELAY CONNECTIONS FOR STYLE B FORMERLY CLASS 8 OR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. r Cm Nntr 3,Fire Alarm,s Base 20989211,Panel WhtlBlk. Head 2098 9201 Head 2098 9201 Head 2098 9201,2120 2098 9202 2098 9202 2098 9202.
4001 4002 2098 9203 2098 9203 2098 9203,4020 or 4100 20989208 2098 9208 2098 9208. 2098 9576 2098 9576 2098 9576, Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 It is recommended that the primary l and the backup 2 lines be in separate wire runs and in compliance with local. requirements, 2098 9211 BASE CONNECTIONS FOR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. Technical Manuals Online http www tech man com,Fire Alarm. 1001 4002 See,4020 or Note,Base 2098 9211 Base 2098 9211.
Head 2098 9201 Head 2098 9201 Head 2098 9201,2098 9202 2098 9202 2098 9202. 2098 9203 2098 9203 2098 9203,2098 9208 2098 9208 2098 9208. 2098 9576 2098 9576 209 576, Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 Refer to wiring diagrams provided with system panel for proper end of line resistor value. 2098 9211 BASE CONNECTIONS FOR STYLE B FORMERLY CLASS B INITIATE CIRCUIT. lote 1 Resistor,rire Alarm,001 4002 Red,4020 or See. 4100 Note Aux Relay Contacts Each,2 Base 2098 9637 Rated 1 Amp at 30VDC or.
Relay Module 2098 9827 0 5 Amp at 12OVAC Resistive. Head 2098 9201,2098 9576 I,2098 9827 Relay Module,See Note 3. Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections. 2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 When wiring relay to base remove resistor black wire from base terminal S3 Wire only one base relay per initiate circuit. 4 For Style D formerly Class A initiate circuit wire per dotted lines and do not use EOL resistor If Style B formerly Class B. initiate circuit refer to wiring diagrams provided with system panel for proper EOL resistor value. 5 For Style D formerly Class A wiring it is recommended that the primary l and the backup 2 lines be in separate wire. runs and in compliance with local requirements,2098 9637 with 2098 9827. BASE AND RELAY CONNECTIONS FOR STYLE B FORMERLY CLASS B OR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. Technical Manuals Online http www tech man com,F onfrIrnI. Panel Red Vi0,5 N O Aux Relay Contacts Each,Base 2098 9211 Rated 1 Amp at 30VDC or. Relav Module 2098 9827 0 5 Amp at 1 POVAC Resistive. Head 20989201,2098 9827 Relay Module,See Note 3, Notes 1 Refer to wiring diagrams 841 687 provided with system panel for proper panel connections.
2 If used remote LED 2098 9808 is polarized observe color coded wiring. 3 When wiring relay to base cut JW Wire only one base relay per initiate circuit. 4 For Style D formerly Class A initiate circuit wire per dotted lines and do not use EOL resistor If Style B formerly Class B. initiate circuit refer to wiring diagrams provided with system panel for proper EOL resistor value. 5 For Style D formerly Class A wiring it is recommended that the primary l and the backup 2 lines be in separate wire. runs and in compliance with local requirements,2098 9211 WITH 20989827. BASE AND RELAY CONNECTIONS FOR STYLE B FORMERLY CLASS B OR STYLE D FORMERLY CLASS A INITIATE CIRCUIT. LIMITATIONS OF SMOKE DETECTORS, The smoke detectors used with these bases are designed to activate and initiate emergency action but will do so. only when used in conjunction with other equipment They are designed for installation in accordance with NFPA. standards 72 l 990 and 72E, Smoke detectors will not work without power AC or DC powered smoke detectors will not work if the power supply. is cut off for any reason, Smoke detectors will not sense fires which start when smoke does not reach the detectors Smoke from fires in. chimneys in walls on roofs or on the other side of closed doors may not reach the smoke detector and alarm it. A detector may not detect a fire developing on another level of a building For this reason detectors shou. l At least one detector will be required in the space between every two beam c Ceiling divided by beams of more than 8 in 20 cm but less than 18 in 46 cm depth l Reduce the coverage area for each detector and mount the detector to the bottom of the beams Important Smoke must enter the chamber of the detector Thus air flow air